Profinet basics
|
|
===============
|
|
Profinet is a field bus that communicates over Ethernet, typically at a speed
|
|
of 100 Mbit/s. For details on Profinet, see
|
|
https://en.wikipedia.org/wiki/PROFINET
|
|
|
|
A detailed introduction to Profinet is given in the book "Industrial
|
|
communication with PROFINET" by Manfred Popp.
|
|
It is available to Profinet members.
|
|
|
|
Profinet devices (IO-devices) are controlled by an PLC (Programmable Logic
|
|
Controller), also known as an IO-controller.
|
|
|
|
|
|
GSD files
|
|
---------
|
|
A GSD (General Station Description) file is an XML file describing a Profinet
|
|
IO-Device. The XML-based language is called GSDML (GSD Markup Language).
|
|
|
|
Note that the GSD file is not used by the p-net stack or application. It is
|
|
a machine readable file describing the capabilities, hardware- and software
|
|
versions etc, and is used by the engineering tool to adjust the PLC settings.
|
|
|
|
The GSD file describes for example which types of pluggable hardware modules
|
|
that can be used in the IO-device. The GSD file is loaded into the
|
|
engineering tool (typically running on a personal computer),
|
|
and a user can then in the tool
|
|
describe which modules that actually should be plugged into the IO-device.
|
|
This is called configuration. Later this information is downloaded to the PLC
|
|
(IO-controller), in a process called commissioning. At startup the PLC will
|
|
tell the IO-device what type of modules it expects to be plugged in.
|
|
If the correct modules not are plugged into the IO-device, the IO-device will
|
|
send an error message back to the PLC.
|
|
|
|
|
|
Startup description
|
|
-------------------
|
|
In the startup of an Profinet IO device (before the IP address has been set) the
|
|
DCP protocol is used. It is like DHCP, but without using a central server.
|
|
|
|
The PLC sends a DCP broadcast message, and all IO Devices on the subnet answer
|
|
with their MAC addresses. The PLC sends a DCP message to the IO Device with
|
|
a specific MAC address, containing which IP address and station name that the
|
|
IO Device should use. The IO Device sets its IP address and station name
|
|
accordingly.
|
|
|
|
Then the PLC starts the actual configuration of the IO device, using the
|
|
DCE/RPC protocol that runs on UDP over IP.
|
|
|
|
After the configuration is done, cyclic data is continuously exchanged between
|
|
the IO-device and the PLC. This communication runs on Ethernet layer 2, i.e.
|
|
the MAC addresses are used for routing frames (the IP protocol is not used in
|
|
those frames).
|
|
|
|
|
|
Nodes classes and device details
|
|
--------------------------------
|
|
Profinet defines three node classes:
|
|
|
|
.. table::
|
|
:widths: 25 50 25
|
|
|
|
+---------------+------------------------------------------------------------------+----------------------------+
|
|
| Node class | Description | | Supported by |
|
|
| | | | this software |
|
|
+===============+==================================================================+============================+
|
|
| IO-Device | "Slave" | Yes |
|
|
+---------------+------------------------------------------------------------------+----------------------------+
|
|
| IO-Controller | "Master", often a PLC. | No |
|
|
+---------------+------------------------------------------------------------------+----------------------------+
|
|
| IO-Supervisor | For commissioning and diagnostics, typically a personal computer | No |
|
|
+---------------+------------------------------------------------------------------+----------------------------+
|
|
|
|
|
|
Depending on the capabilities, different conformance classes are assigned.
|
|
|
|
+------------------------+---------------------------------------------+----------------------------+----------------------------+
|
|
| | Conformance | Description | | Supported by | | Communication |
|
|
| | class (CC) | | | this software | | profile (CP) |
|
|
+========================+=============================================+============================+============================+
|
|
| A | Wireless is only allowed for class A | Yes | CP 3/4 |
|
|
+------------------------+---------------------------------------------+----------------------------+----------------------------+
|
|
| B | Class A + SNMP (network topology detection) | Yes | CP 3/5 |
|
|
+------------------------+---------------------------------------------+----------------------------+----------------------------+
|
|
| B (PA) | Class B + System redundancy | No | |
|
|
+------------------------+---------------------------------------------+----------------------------+----------------------------+
|
|
| C | Class B + IRT communication | No | CP 3/6 |
|
|
+------------------------+---------------------------------------------+----------------------------+----------------------------+
|
|
| D | Uses time sensitive networking Ethernet | No | CP 3/7 |
|
|
+------------------------+---------------------------------------------+----------------------------+----------------------------+
|
|
|
|
The first digit in the Communication Profile (CP) is the Communication Profile Family (CPF). Profinet and Profibus are CPF 3,
|
|
while for example Ethercat is CPF 12.
|
|
|
|
Communication profiles CP 3/1 and CP 3/2 are for Profibus. The CP 3/3 was used for the legacy Profinet CBA.
|
|
|
|
Real Time Class:
|
|
|
|
* Real Time Class 1 Mandatory for conformance class A, B, C
|
|
* Real Time Class 2 (legacy) Only for legacy startup mode for conformance class C.
|
|
* Real Time Class 3 = IRT (Isochronous Real Time) Mandatory for conformance class C
|
|
* Real Time Class UDP For cross-network real time communication. Optional for conformance class A, B, C
|
|
* Real Time Class STREAM for conformance class D.
|
|
|
|
This software supports Real Time Class 1.
|
|
|
|
|
|
MAC addresses
|
|
-------------
|
|
If your device has two Ethernet connectors (ports), then it typically uses an Ethernet
|
|
switch chip with three data connections::
|
|
|
|
Port X1 P1 Port X1 P2
|
|
| |
|
|
| |
|
|
| |
|
|
+--+-----------------+--+
|
|
| |
|
|
| Ethernet Switch |
|
|
| |
|
|
+----------+------------+
|
|
|
|
|
|
|
|
|
|
|
Profinet interface X1
|
|
|
|
The device has one interface and two ports.
|
|
For Profinet conformance class B and higher, there are three assigned MAC addresses:
|
|
|
|
* Profinet interface X1 (main MAC address or device MAC address)
|
|
* Port X1 P1
|
|
* Port X1 P2
|
|
|
|
The MAC addresses for X1 P1 and X1 P2 are used by the LLDP protocol for neighbor detection.
|
|
|
|
There are examples of Profinet controllers with more than one interface (having more than one port each).
|
|
Each interface has its own IP address. Each port has its own MAC address.
|
|
|
|
|
|
Communication
|
|
-------------
|
|
|
|
Profinet uses three protocol levels:
|
|
|
|
+-----------------------------+--------------------+-------------+---------------+----------------------------+
|
|
| Protocol | | Typical | Description | Ethertype | | Supported by |
|
|
| | | cycle time | | | | this software |
|
|
+=============================+====================+=============+===============+============================+
|
|
| TCP/IP (UDP actually) | 100 ms | | 0x0800 = IPv4 | Yes |
|
|
+-----------------------------+--------------------+-------------+---------------+----------------------------+
|
|
| RT (Real Time) | 10 ms | | 0x8892 | Yes |
|
|
+-----------------------------+--------------------+-------------+---------------+----------------------------+
|
|
| IRT (Isochronous Real-Time) | 1 ms | | 0x8892? | No |
|
|
+-----------------------------+--------------------+-------------+---------------+----------------------------+
|
|
|
|
Profinet uses IPv4 only (not IPv6).
|
|
|
|
|
|
Overview of all protocols used in a Profinet Application
|
|
--------------------------------------------------------
|
|
|
|
A typical Profinet application needs to handle a multitude of protocols.
|
|
The p-net stack implements some of them, while others are optional.
|
|
For example HTTP is used by some IO-devices for additional configuration via
|
|
a web page, but should be implemented outside the Profinet stack itself.
|
|
|
|
+-------+----------+-------------+-----------------+-----------------------+---------------------------------+
|
|
| Layer | Protocol | Addressing | | Content | Protocol | Notes |
|
|
| | | | | description | | |
|
|
+=======+==========+=============+=================+=======================+=================================+
|
|
| 4 | TCP | Port | SSH = 22 | Remote login on Linux |
|
|
| | | +-----------------------+---------------------------------+
|
|
| | | | HTTP = 80 + 443 | Web server for configuration |
|
|
+-------+----------+-------------------------------+-----------------------+---------------------------------+
|
|
| 4 | UDP | Port | DHCP = 67 + 68 | IP address assignment |
|
|
| | | +-----------------------+---------------------------------+
|
|
| | | | SNMP = 161 + 162 | Network topology query |
|
|
| | | +-----------------------+---------------------------------+
|
|
| | | | PNIO-CM = 34964 | Profinet start-up, uses DCE/RPC |
|
|
+-------+----------+-------------+-----------------+-----------------------+---------------------------------+
|
|
| 3 | IPv4 | IP address | Protocol number | ICMP = 1 | Used by ping |
|
|
| | | | +-----------------------+---------------------------------+
|
|
| | | | | TCP = 6 | Transmission control protocol |
|
|
| | | | +-----------------------+---------------------------------+
|
|
| | | | | UDP = 17 | User Datagram Protocol |
|
|
+-------+----------+-------------+-----------------+-----------------------+---------------------------------+
|
|
| 2 | Ethernet | MAC address | Ethertype | LLDP = 0x88CC | Link layer discovery |
|
|
| | | | +-----------------------+---------------------------------+
|
|
| | | | | ARP = 0x0806 | IP address lookup |
|
|
| | | | +-----------------------+---------------------------------+
|
|
| | | | | IPv4 = 0x0800 | Internet protocol |
|
|
| | | | +-----------------------+---------------------------------+
|
|
| | | | | PN-DCP = 0x8892 | Profinet start-up |
|
|
| | | | +-----------------------+---------------------------------+
|
|
| | | | | Profinet RT = 0x8892 | PNIO_PS = Cyclic IO data |
|
|
| | | | +-----------------------+---------------------------------+
|
|
| | | | | (VLAN = 0x8100) | Not really a protocol |
|
|
| | | | +-----------------------+---------------------------------+
|
|
| | | | | (VLAN = 0x9100) | For double tagged frames |
|
|
+-------+----------+-------------+-----------------+-----------------------+---------------------------------+
|
|
|
|
Profinet Profiles
|
|
-----------------
|
|
There are a number of Profinet application profiles defined, for example
|
|
PROFIenergy and PROFIdrive. These defines for example the cyclic data should
|
|
be interpreted.
|
|
|
|
Profiles use the API (Application Program Identifier) concept for telling
|
|
that profile-specific data is transferred.
|
|
|
|
|
|
Slots and modules
|
|
-----------------
|
|
A Profinet IO-device has typically a number of slots where (hardware) modules
|
|
can be placed. A module can have subslots where submodules are placed.
|
|
Each submodule have a number of channels (for example digital inputs).
|
|
|
|
Each API has its own collection of slots.
|
|
|
|
TODO Example
|
|
|
|
* Module
|
|
* Submodule
|
|
* Channels
|
|
|
|
Channels are always connected to submodules (rather than to modules).
|
|
|
|
Addressing a channel
|
|
|
|
* Slot
|
|
* Subslot
|
|
* Index
|
|
|
|
First usable slot is slot number 1. Slot 0 is used for the IO-device itself,
|
|
and does not have any input/output data. Instead it has diagnostic information
|
|
for the IO-device.
|
|
|
|
If compile time setting PNET_MAX_SLOTS is 5, then the slots are numbered 0-4.
|
|
The setting PNET_MAX_SUBSLOTS controls the number of subslots per slot,
|
|
but there is no fixed relation to which subslot numbers will be used.
|
|
Subslot numbers in the range 0-0x9FFF might be used.
|
|
|
|
The GSD file pretty much describes the hardware: slots (and subslots), and
|
|
the modules (and submodules) that can be placed in the slots. The file does
|
|
not describe which modules that actually have been placed in each slot for
|
|
each device. That is done during the setup (configuration) in the engineering
|
|
tool during PLC programming.
|
|
|
|
Also in the GSD file is description on the data exchange?
|
|
|
|
+----------------------+-------------------------------------+
|
|
| Type | Description |
|
|
+======================+=====================================+
|
|
| Compact field device | Not possible to change modules etc? |
|
|
+----------------------+-------------------------------------+
|
|
| Modular field device | Change modules at configuration? |
|
|
+----------------------+-------------------------------------+
|
|
|
|
|
|
Payload
|
|
-------
|
|
The Profinet payload is sent as big endian (network endian) on the wire.
|
|
|
|
The maximum data (and status) size in total in each direction for a device is 1440 bytes.
|
|
If this is consumed by a single subslot the maximum data size is 1438 byte (plus one or two bytes for IOPS and IOCS).
|
|
See the IOData entry in the GSDML specification.
|
|
|
|
If the IOPS (producer status) for a subslot goes to BAD, the PLC will indicate an error
|
|
"User data failure of hardware component".
|
|
It will persist until the communication is restarted to the IO-device.
|
|
|
|
|
|
I&M data records
|
|
----------------
|
|
This is Identification & Maintenance records, which are human-readable
|
|
information about the model type, software version etc.
|
|
Some fields are writable, for example where the device is located.
|
|
|
|
Up to I&M15 is described in the standard. The p-net stack supports I&M0 - I&M4.
|
|
You must support writing to I&M1-3 for at least one of the DAP submodules.
|
|
|
|
+-------------+-----------+-----------------------+--------------------------------------------------------------+
|
|
| Data record | Mandatory | Controller can write? | Description |
|
|
+=============+===========+=======================+==============================================================+
|
|
| I&M0 | Yes | No | Vendor ID, serial number. Hardware and software version etc. |
|
|
+-------------+-----------+-----------------------+--------------------------------------------------------------+
|
|
| I&M1 | No | Yes | Tag function and location |
|
|
+-------------+-----------+-----------------------+--------------------------------------------------------------+
|
|
| I&M2 | No | Yes | Date. Format "1995-02-04 16:23" |
|
|
+-------------+-----------+-----------------------+--------------------------------------------------------------+
|
|
| I&M3 | No | Yes | Descriptor |
|
|
+-------------+-----------+-----------------------+--------------------------------------------------------------+
|
|
| I&M4 | No | Yes | Signature. Only for functional safety. |
|
|
+-------------+-----------+-----------------------+--------------------------------------------------------------+
|
|
|
|
There is also I&M0 Filterdata, which is read only.
|
|
|
|
|
|
Startup modes
|
|
-------------
|
|
The startup mode was changed in Profinet 2.3, to "Advanced". The previous
|
|
startup mode is now called "Legacy".
|
|
|
|
|
|
Net load class
|
|
--------------
|
|
|
|
* I
|
|
* II
|
|
* III
|
|
|
|
|
|
Alarm types
|
|
-----------
|
|
A process alarm describes conditions in the monitored process, for example
|
|
too high temperature.
|
|
|
|
A diagnostic alarm describes conditions in the IO Device itself, for example
|
|
a faulty channel or short circuit. Diagnostic alarms are also stored in the IO-Device.
|
|
|
|
Description of supported alarm types:
|
|
|
|
+------------------------------------------+--------+-----------------------------------------------------------+
|
|
| Name | Hex | Description |
|
|
+==========================================+========+===========================================================+
|
|
| Diagnosis | 0x0001 | There is something wrong with the IO device itself |
|
|
+------------------------------------------+--------+-----------------------------------------------------------+
|
|
| Process | 0x0002 | There is something wrong with the process, for |
|
|
| | | example too high temperature. High priority. |
|
|
+------------------------------------------+--------+-----------------------------------------------------------+
|
|
| Pull | 0x0003 | Submodule pulled from subslot. |
|
|
+------------------------------------------+--------+-----------------------------------------------------------+
|
|
| Plug | 0x0004 | Module/submodule plugged into slot/subslot. |
|
|
+------------------------------------------+--------+-----------------------------------------------------------+
|
|
| Controlled by supervisor | 0x0008 | |
|
|
+------------------------------------------+--------+-----------------------------------------------------------+
|
|
| Released | 0x0009 | |
|
|
+------------------------------------------+--------+-----------------------------------------------------------+
|
|
| Plug wrong submodule | 0x000A | Wrong module/submodule plugged into slot/subslot. |
|
|
+------------------------------------------+--------+-----------------------------------------------------------+
|
|
| Return of submodule | 0x000B | |
|
|
+------------------------------------------+--------+-----------------------------------------------------------+
|
|
| Diagnosis disappears | 0x000C | A kind of diagnosis alarm |
|
|
+------------------------------------------+--------+-----------------------------------------------------------+
|
|
| Port data change notification | 0x000E | Port up, or peer changes name. A kind of diagnosis alarm. |
|
|
+------------------------------------------+--------+-----------------------------------------------------------+
|
|
| Pull module | 0x001F | Module pulled from slot. |
|
|
+------------------------------------------+--------+-----------------------------------------------------------+
|
|
|
|
Only process alarms are sent with high prio, all other alarms use low prio.
|
|
|
|
|
|
Diagnosis
|
|
---------
|
|
Diagnosis alarms are sent to indicate for example short-circuit on an output.
|
|
|
|
To localize the diagnosis source, these values are required:
|
|
|
|
* API
|
|
* Slot
|
|
* Subslot
|
|
* Channel number (Use 0x8000 for "whole submodule")
|
|
* Accumulative (true when describing a channel group)
|
|
* Direction (in or out. Use "manufacturer specific" for "whole submodule")
|
|
|
|
Do not update diagnosis information at a higher frequency than 1 Hz.
|
|
|
|
|
|
Logbook
|
|
-------
|
|
A logbook is a circular buffer with at least 16 entries. The IO-controller can
|
|
read out entire logbook. Each entry contains:
|
|
|
|
* A timestamp
|
|
* Error codes (4 bytes)
|
|
* A manufacturer specific entry detail (uint32_t)
|