Codesys Details
|
|
===============
|
|
This page contains additional information on how to use the Codesys soft PLC.
|
|
|
|
|
|
Adjust PLC timing settings
|
|
--------------------------
|
|
It is possible to adjust the cycle time that the IO-controller (PLC) is using
|
|
for cyclic data communication with an IO-device.
|
|
|
|
In the left menu, double-click the "P_Net_Sample_App", and open the "General"
|
|
tab. The "Communication" section shows the send clock in milliseconds, as read
|
|
from the GSDML file. By using the "Reduction ratio" you can slow down the
|
|
communication, by multiplying the cycle time by the factor given in the
|
|
dropdown.
|
|
|
|
It is also possible to increase the watchdog time, after which the PLC will set
|
|
an alarm for missing incoming cyclic data. The watchdog will also shut down the
|
|
communication, and trigger a subsequent restart of communication.
|
|
|
|
In case of problems, increase the reduction ratio (and timeout) value a lot,
|
|
and then gradually reduce it to find the smallest usable value.
|
|
|
|
|
|
Displaying errors
|
|
-----------------
|
|
Click on the IO-device in the tree structure in the left part of the screen.
|
|
Use the "Log" tab to display errors.
|
|
|
|
|
|
Connection status
|
|
-----------------
|
|
Go to the Profinet IO-device page, and see the "PNIO IEC objects" tab. Expand
|
|
the topmost row. The states of these boolean fields are shown:
|
|
|
|
* xRunning: Periodic data is sent
|
|
* xBusy: The controller is trying to connect to the IO-device
|
|
* xError: Failure to connect to the IO-device
|
|
|
|
If there is no connection at all to the IO-device, the state will shift to
|
|
xBusy from xError once every 5 seconds.
|
|
|
|
|
|
Change IP address of IO-device
|
|
------------------------------
|
|
Change the IP address by double-clicking the "P_Net_Sample_App" node
|
|
in the left menu, using the "General" tab. Set the IP-address to new value.
|
|
|
|
The IO-controller will send the new IP address in a "DCP Set" message to the
|
|
IO-device having the given station name. Then it will use ARP messages to
|
|
the IO-device to find its MAC address, and to detect IP address collisions.
|
|
|
|
|
|
Scan for devices, assign IP address, reset devices and change station name
|
|
--------------------------------------------------------------------------
|
|
|
|
Scan
|
|
^^^^
|
|
In the left side menu, right-click the PN_Controller and select "Scan for
|
|
devices". The running IO-devices will show up, and it is possible to see which
|
|
modules are plugged into which slot.
|
|
Note that the texts in the columns "Device name" and "Device type" are from the
|
|
available GSDML files in Codesys. If a corresponding GSDML file not has been
|
|
loaded, the text "Attention: The device was not found in the repository" is
|
|
shown together with the Vendor-ID and Product-ID.
|
|
|
|
This is implemented in Codesys by sending the "Ident request, all" DCP
|
|
message from the IO-controller.
|
|
It works also if there are no IO-devices loaded in the left side hierarchy menu.
|
|
An IO-device will respond with the "Ident OK" DCP message. Then the IO-controller
|
|
will do a "Read implicit request" for "APIData", on which the IO device
|
|
responds with the APIs it supports. A similar request for
|
|
"RealIdentificationData for one API" is done by the IO-controller, on which the
|
|
IO-device responds which modules (and submodules) are plugged into which slots
|
|
(and subslots).
|
|
|
|
Factory reset
|
|
^^^^^^^^^^^^^
|
|
To factory reset a device, select it in the list of scanned devices and click
|
|
the "reset" button.
|
|
|
|
At a factory reset, the IO-controller sends a "Set request" DCP message
|
|
with suboption "Reset factory settings". After sending a response, the
|
|
IO-device will do the factory reset and also send a LLDP message with the
|
|
new values. Then the IO-controller sends a "Ident request, all", to which
|
|
the IO-device responds.
|
|
|
|
Set name and IP
|
|
^^^^^^^^^^^^^^^
|
|
To modify the station name or IP address, change the corresponding fields
|
|
in the list of scanned devices, and the click "Set name and IP".
|
|
|
|
The IO-controller sends a "Set request" DCP message
|
|
with suboptions "Name of station" and "IP parameter". After sending a
|
|
response, the IO-device will change IP address and station name. It will
|
|
also send a LLDP message with the new values. Then the
|
|
IO-controller sends a "Ident request, all", to which the IO-device responds.
|
|
|
|
Flash LED
|
|
^^^^^^^^^
|
|
There is functionality to flash a LED on an IO-device. Select your device in
|
|
the list of scanned devices, and click the "Blink LED" button. The button
|
|
remains activated until you click it again.
|
|
|
|
LED-blinking is done by sending the "Set request" DCP message with suboption
|
|
"Signal" once every 5 seconds as long as the corresponding button is activated.
|
|
|
|
Identification & Maintenance (I&M) data
|
|
^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^
|
|
In order the read Identification & Maintenance (I&M) data, the device needs to
|
|
be present as an IO-device connected to the IO-controller in the left side menu.
|
|
Select the device in the list of scanned devices, and click the "I&M" button.
|
|
|
|
Reading I&M data is done by the IO-controller by sending four "Read implicit"
|
|
request DCP messages, one for each of I&M0 to I&M3.
|
|
|
|
When writing I&M data from Codesys, it will send a connect, write and release.
|
|
|
|
|
|
Writing and reading IO-device parameters
|
|
----------------------------------------
|
|
The parameters for different submodules are written as part of normal startup.
|
|
|
|
To adjust the values sent at startup, you must first be offline.
|
|
Then double-click the DIO_8xLogicLevel device in the left menu. Use the
|
|
General tab, and the Settings part of the page. Click the corresponding
|
|
value in the table, and adjust it.
|
|
|
|
While offline (with regards to the PLC, it is possible to manually trigger
|
|
parameter reading and writing. Right-click the parameter you would like
|
|
to send, and select "Write to device". It is also possible to read a
|
|
parameter similarly.
|
|
|
|
To read all or write all parameters, use the corresponding buttons.
|
|
When clicking the "Write All Values" icon, one write request is sent per
|
|
parameter.
|
|
|
|
|
|
Forcing cyclic data values
|
|
--------------------------
|
|
To force an output value from the PLC, open the PLC_PRG window while online.
|
|
In the table on the top of the page, on the line you would like to force click the "Prepared value"
|
|
until it shows "TRUE". Use the line "out_pin_LED" if running the sample application.
|
|
Right-click on the line, and select "Force all values ...". The new value is sent from the PLC to the IO-device.
|
|
A red `F` symbol is shown.
|
|
To stop forcing the value, right-click it and select "Unforce all values ...".
|
|
|
|
|
|
Displaying alarms sent from IO-device
|
|
-------------------------------------
|
|
Incoming process alarms and diagnosis alarms appear on multiple places in
|
|
the Codesys desktop application.
|
|
|
|
* Codesys Raspberry Pi: The "Log" tab show process and diagnosis alarms.
|
|
* PN_Controller: The "Log" tab show process and diagnosis alarms.
|
|
* IO-device: The "Log" tab show process and diagnosis alarms. The
|
|
“Status” tab shows alarms related to built-in (DAP) modules.
|
|
* Plugged module in IO-device: Process and diagnosis alarms are displayed on
|
|
the “Status” tab.
|
|
|
|
|
|
Setting output producer status (IOPS)
|
|
-------------------------------------
|
|
Normally Codesys will set the Output PS to GOOD (0x80 = 128) when running.
|
|
Clicking the "Output PS" checkbox on the "IOxS" tab on the Profinet IO-device
|
|
sets the value to BAD (0).
|
|
|
|
|
|
Enabling checking of peer stationname and port ID
|
|
-------------------------------------------------
|
|
It is possible to have the IO-device verify that it is connected to the
|
|
correct neighbour (peer) by checking its station name and port ID (as sent
|
|
in LLDP frames by the neighbour).
|
|
|
|
Double-click the “P_Net_Sample_App” node in the left menu. On the "options"
|
|
tab in the resulting window, use the fields "Peer station" and "port". It
|
|
seems only possible to select station names from other devices or controllers
|
|
already available in the project.
|
|
|
|
During startup the PLC will send the given values to the IO-Device via a
|
|
write command. If the correct neighbour is not present, an alarm will be sent
|
|
by the IO-device to the PLC.
|
|
|
|
|
|
Writing PLC programs
|
|
--------------------
|
|
Documentation of available function blocks is found at
|
|
https://help.codesys.com/webapp/_pnio_f_profinet_io_configuration;product=core_ProfinetIO_Configuration_Editor
|
|
|
|
|
|
Using the Echo module
|
|
---------------------
|
|
The echo module will receive an integer and a float from the PLC, and multiply them with a constant
|
|
value before sending them back to the PLC. The multiplier is module parameter, and can be adjusted
|
|
at startup. The integer is an unsigned 32 bit integer, and the float is a single precision float
|
|
(32 bits).
|
|
|
|
To test it, unplug any existing modules, and plug one Echo module into slot 1.
|
|
|
|
Enter this program::
|
|
|
|
PROGRAM PLC_PRG
|
|
VAR
|
|
out_echo_int: UDINT;
|
|
out_echo_float: REAL;
|
|
in_echo_int: UDINT;
|
|
in_echo_float: REAL;
|
|
temp_int: UDINT;
|
|
temp_float: REAL;
|
|
END_VAR
|
|
|
|
out_echo_int := 1000001;
|
|
out_echo_float := 1001.23456;
|
|
|
|
temp_int := in_echo_int;
|
|
temp_float := in_echo_float;
|
|
|
|
On the Echo_module page, use the "PNIO Module I/O Mapping" to connect the
|
|
four program variables to the corresponding channels. Connect "in_echo_float" to
|
|
"Input float to controller" etc.
|
|
|
|
Start the PLC, and go online to follow the values. You can force (described elsewhere)
|
|
the ``out_echo_int`` and ``out_echo_float`` values to study how the resulting
|
|
input values from the IO-device changes.
|