Creating applications and porting to new hardware
|
||
|
|
=================================================
|
||
|
|
|
||
|
|
Create your own application
|
||
|
|
---------------------------
|
||
|
|
If you prefer not to implement some of the callbacks, set the corresponding
|
||
|
|
fields in the configuration struct to NULL instead of a function pointer.
|
||
|
|
See the API documentation on which callbacks that are optional.
|
||
|
|
|
||
|
|
To read output data from the PLC, use ``pnet_output_get_data_and_iops()``.
|
||
|
|
To write data to the PLC (which is input data in Profinet terminology), use
|
||
|
|
``pnet_input_set_data_and_iops()``.
|
||
|
|
|
||
|
|
|
||
|
|
Adapt to other hardware
|
||
|
|
-----------------------
|
||
|
|
You need to adapt the implementation to your specific hardware.
|
||
|
|
|
||
|
|
This includes for example:
|
||
|
|
|
||
|
|
* For Linux, adjust the networking and LED scripts in PNAL
|
||
|
|
* Implement the callback to control the "Signal" LED.
|
||
|
|
|
||
|
|
|
||
|
|
Required features of the hardware or operating system
|
||
|
|
-----------------------------------------------------
|
||
|
|
|
||
|
|
* It should be possible to send and receive raw (layer 2) Ethernet frames
|
||
|
|
* It should be possible to store data between runs, in a file system or some nonvolatile memory
|
||
|
|
* For conformance class B, there needs to be an SNMP implementation that
|
||
|
|
the p-net stack can use.
|
||
|
|
|
||
|
|
|
||
|
|
General requirements
|
||
|
|
--------------------
|
||
|
|
It should be possible to do a factory reset without an engineering tool. For
|
||
|
|
example a hardware switch can be used. Routing of Ethernet frames must not be
|
||
|
|
affected by a factory reset.
|
||
|
|
|
||
|
|
A Profinet signal LED must be visible on the IO-Device. A callback is available
|
||
|
|
from p-net to control the signal LED, so you can implement your board specific
|
||
|
|
hardware.
|
||
|
|
|
||
|
|
Connectors and cables should fulfill the requirements in "PROFINET Cabling and
|
||
|
|
Interconnection Technology". For recommended diagnosis indicators (for example
|
||
|
|
LEDs) see "Diagnosis for PROFINET".
|
||
|
|
Consider the housing (often IP65) and grounding of the device.
|
||
|
|
In general the MAC address of the device should be visible when installed.
|
||
|
|
|
||
|
|
Hardware requirements for the Ethernet ports:
|
||
|
|
|
||
|
|
* At least 100 Mbit/s full duplex
|
||
|
|
* Standard and crossover cables should be handled
|
||
|
|
* Auto polarity
|
||
|
|
* Auto negotiation (should be possible to turn off for fast startup)
|
||
|
|
|
||
|
|
|
||
|
|
Interacting with other parts of your application software
|
||
|
|
---------------------------------------------------------
|
||
|
|
When the PLC sends a "factory reset" command, not only the p-net stack but
|
||
|
|
also the rest of your application should be reset to factory settings.
|
||
|
|
|
||
|
|
If there is a method to do a factory reset of your application, it should also
|
||
|
|
reset the p-net stack.
|
||
|
|
|
||
|
|
It is possible to set the IP-address, netmask and gateway address via Profinet
|
||
|
|
from a PLC. Consider how this affects other aspects of your application.
|
||
|
|
|
||
|
|
Serial number, software version, model name etc should be available for the
|
||
|
|
p-net stack to use.
|
||
|
|
|
||
|
|
|
||
|
|
Minimum cycle time for your application and hardware
|
||
|
|
----------------------------------------------------
|
||
|
|
At PLC configuration, there are two adjustable parameters regarding the
|
||
|
|
cyclic data timing for an IO-device. One basically controls the
|
||
|
|
frame-to-frame transmission interval (given as a multiple of the cycle time),
|
||
|
|
and the other one controls the PLC watchdog timeout setting.
|
||
|
|
The watchdog triggers an alarm when a number of consecutive cyclic data
|
||
|
|
frames from the IO-device are missing.
|
||
|
|
|
||
|
|
During conformance testing, the PLC watchdog timeout setting is 3 x
|
||
|
|
frame-to-frame interval times, ie the PLC will trigger an alarm if three
|
||
|
|
consecutive cyclic data frames are missing. Thus the smallest allowed
|
||
|
|
frame-to-frame interval given in the GSDML file must take the smallest
|
||
|
|
useful PLC watchdog timeout setting into account.
|
||
|
|
|
||
|
|
There can be different factors limiting the ability to send Profinet frames at
|
||
|
|
a regular pace:
|
||
|
|
|
||
|
|
* The initial work at Profinet communication startup should not cause
|
||
|
|
delays in the cyclic data transmission once started.
|
||
|
|
* The hardware needs to keep up with the steady-state sending and receiving
|
||
|
|
of Profinet cyclic data.
|
||
|
|
* Other work done by the Profinet application, for example work done in
|
||
|
|
callbacks, might slow down the communication.
|
||
|
|
* Operating system jitter, which basically is that the operating system is
|
||
|
|
busy doing other work, will cause frame delays.
|
||
|
|
* Using a network interface connected via USB can cause additional frame
|
||
|
|
delays.
|
||
|
|
|
||
|
|
For real-time operating systems (RTOS) for example rt-kernel, the
|
||
|
|
frame-to-frame transmission will have little jitter.
|
||
|
|
|
||
|
|
For non-real-time operating systems, for example Linux, the limiting factor
|
||
|
|
is typically the jitter caused by the operating system.
|
||
|
|
See the page on Linux timing in this documentation for ideas on improving
|
||
|
|
Linux real-time properties.
|
||
|
|
|
||
|
|
|
||
|
|
Measure Profinet frame transmission jitter
|
||
|
|
^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^
|
||
|
|
Set the PLC watchdog time to 100 x frame interval, to avoid any alarms
|
||
|
|
from the PLC.
|
||
|
|
Use Wireshark to record cyclic data transmission for a few minutes.
|
||
|
|
Plot the maximum frame-to-frame transmission interval (see the page on
|
||
|
|
capturing Ethernet packets in this documentation).
|
||
|
|
This will show which PLC watchdog setting you need in order not to trigger
|
||
|
|
"missing frame" alarms.
|
||
|
|
|
||
|
|
For example if the transmission interval is 1 ms but there sometimes is a 10 ms
|
||
|
|
delay between the frames, then you need to use the next standard PLC timeout
|
||
|
|
value which is 12 ms. In order to handle that with a watchdog setting of 3 x
|
||
|
|
frame interval, you need to use a minimum cycle time of 4 ms (as
|
||
|
|
will be stated in your GSDML file).
|
||
|
|
|
||
|
|
|
||
|
|
Example measurement results
|
||
|
|
^^^^^^^^^^^^^^^^^^^^^^^^^^^
|
||
|
|
Measurements with p-net on a XMC4800 board running rt-kernel shows that the
|
||
|
|
hardware is able to send frames with a periodicity of 1 ms with little jitter.
|
||
|
|
The liming factor is that the PLC watchdog timeout value needs to be 12 ms,
|
||
|
|
due to the time it takes for the first cyclic data frame to be sent from
|
||
|
|
the IO-device.
|
||
|
|
A GSDML file should state that the smallest allowed cycle time is 4 ms.
|
||
|
|
|
||
|
|
Similar measurements on a Raspberry Pi 3B+ show that it is possible to send
|
||
|
|
frames with a cycle time of 1 ms. However there is sometimes a frame-to-frame
|
||
|
|
interval of up to 40 ms, resulting in that a GSDML file should state that the
|
||
|
|
minimum frame interval is 16 ms.
|